Server Room Cooling Calculator: BTU/h, Tons & AC Units
Cooling load from IT power in BTU/h, kW and tons, and the number of AC units with N+1.
- Total heat
- 4,896 W
- In kilowatts of cooling
- 4.9 kW
- In tons of refrigeration
- 1.39 TR
- Equivalent in Indonesian 'PK' sizes (9,000 BTU/h each)
- 1.9 PK
- Units without a spare (N)
- 1
Formula and sources
Heat = (IT power × (1 + UPS/PDU losses) + other heat) × (1 + margin); all the electrical power of IT equipment ends up as heat BTU/h = watts × 3.41214 (1 BTU/h = 0.2930711 W); 1 ton of refrigeration = 12,000 BTU/h = 3.517 kW AC units = ⌈BTU/h ÷ capacity per unit⌉, + 1 for N+1
When to use the Server Room Cooling
Electrical watts become heat
Nearly all the power that servers, switches and storage draw turns into heat in the room. The cooling load is therefore worked out straight from the equipment watts, plus UPS and PDU losses, lights and people.
BTU/h, kW, tons and PK
AC capacity is quoted in BTU/h, kW or tons of refrigeration. One ton is 12,000 BTU/h, about 3.5 kW. Always compare the BTU/h or kW in the unit's specification, not the model name.
N+1 redundancy
Server-room AC runs nonstop and will need servicing. With N+1, one unit can fail or be serviced without the room overheating. The result shows the unit count with and without the spare.
A worked example
A 3,500 W rack with 8% UPS losses, 300 W of other heat and a 20% margin comes to about 4,900 W or 16,700 BTU/h. One 18,000 BTU/h unit is enough, and N+1 means installing two.
Frequently asked questions
What size AC does a small server room need?
Work from the equipment power, not the floor area. A 1,000 W rack with nothing else produces about 3,400 BTU/h; with a margin, a 5,000–9,000 BTU/h unit is usually enough.
How do I find the equipment power?
Read the load on the UPS or PDU display, or measure with a power meter. The figure on a power supply's label is its maximum and usually far above real use.
Does the room size matter?
Heat through walls, the roof and sunlight adds to the load. For a room with outside walls or windows, add an estimate under other heat or raise the margin.