UPS Calculator: VA Rating & Battery Runtime

UPS rating in VA and watts and the battery runtime estimated with Peukert's law.

Calculated in your browserServer & Storage
W
The real power of the equipment to protect (from its label or a power meter).
The watts ÷ VA ratio in the UPS specification, often 0.6–1.0.
%
V
Ah
%
VRLA AGM UPS batteries are about 1.05–1.15; 1.00 = no correction.
h
Ah capacity is usually rated at the 20-hour rate (C20).
Minimum UPS rating
625 VA
Estimated runtime (Peukert)
17.7 min
In watts
563 W
Energy-only estimate (no Peukert)
25.9 min
Battery bank voltage
24 V
Battery bank energy
216 Wh
Current from the batteries
20.83 A
  • Discharge current above 1C: at such a rate real batteries give less than any formula predicts. Use the UPS maker's runtime table.

Formula and sources

UPS VA = load (W) ÷ power factor × (1 + headroom); watts = load × (1 + headroom) Battery current I = load ÷ inverter efficiency ÷ bank voltage; runtime (Peukert) = H × (C ÷ (I × H))^k hours, C = bank Ah at the H-hour rating Energy-only estimate = bank Wh × efficiency ÷ load

When to use the UPS Size & Battery Runtime

  • Watts and VA

    A UPS has two limits, VA and watts. A 450 W load on a UPS with a 0.9 power factor needs 500 VA, and with 25% headroom about 625 VA. Choose a UPS whose two ratings both exceed the need.

  • Why runtime is shorter than the Wh sum

    Lead-acid batteries deliver less capacity when drained quickly. A UPS empties them in minutes, far faster than the 20-hour rate behind the Ah label, so Peukert's law gives a more realistic estimate.

  • Batteries in series and parallel

    Two 12 V batteries in series make a 24 V bank with the same Ah. Adding parallel strings adds Ah and lengthens runtime. Follow the bank voltage your UPS requires.

  • Why headroom matters

    A UPS that runs close to 100% runs hotter and gives shorter runtime. 20–30% headroom also leaves room for future equipment.

Frequently asked questions

How long will a 1,000 VA UPS last?

It depends on the load and the batteries inside, not the VA figure. Enter the load, battery voltage and Ah to estimate, then compare with the maker's runtime table.

Where do I find the power factor?

Divide the watt rating by the VA rating in the specification. A 1,500 VA / 900 W UPS has a power factor of 0.6; 1,500 VA / 1,350 W has 0.9.

Does this work for lithium batteries?

Lithium batteries are far less affected by the discharge rate than lead-acid ones. Use a Peukert exponent close to 1.0 and follow the maker's current limits.