Circuit Breaker Size Calculator (IEC and NEC)
Breaker rating from the load's watts or amps, with IEC 60898-1 or NEC standard sizes.
- Minimum ratingload current + headroom
- 16.91 A
- Load on the breaker
- 84.5%
- The cable must carry at least the breaker's rating; choose its size from an ampacity table, not from the load alone.
Standard ratings near the requirement
| Rating (A) | Load (%) | Status |
|---|---|---|
| 10 | 169.1 | too small |
| 13 | 130.1 | too small |
| 16 | 105.7 | too small |
| 20 | 84.5 | enough |
| 25 | 67.6 | enough |
| 32 | 52.8 | enough |
Formula and sources
Single-phase current = P ÷ (V × PF); three-phase = P ÷ (√3 × V × PF) NEC: minimum rating = noncontinuous load + 1.25 × continuous load (210.20(A)); IEC: minimum rating = load current Minimum × (1 + headroom); breaker = the smallest standard rating ≥ the minimum
- IEC 60898-1 clause 5.3.2 — preferred values of rated current (IS/IEC 60898-1:2002)
- BEAMA — Guide to low voltage circuit-breaker standards (BS EN 60898)
- NFPA 70 (NEC) 240.6(A) and 210.20(A) — standard ratings and 125% of continuous load
When to use the Circuit Breaker Size
From watts to amps
Breakers are chosen by current, not power. Single-phase current is the power divided by the voltage and power factor; three-phase current is divided by √3 as well. Enter the voltage used where you are.
IEC 60898-1 preferred ratings
Household MCBs in 230/400 V countries follow the preferred values 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A. The calculator picks the smallest one that is not below the load current plus your headroom.
The NEC 125% rule
In the United States the NEC requires a breaker rated at least the noncontinuous load plus 125% of the continuous load, meaning load that runs three hours or more. Standard ratings run 15, 20, 25, 30 A and up.
How loaded the breaker is
The table lists the ratings around your requirement and the load on each. A breaker loaded close to 100% for long periods trips more easily when the panel runs warm or loads start together.
Frequently asked questions
What about Indonesian PLN connections?
PLN sets a home's connection with the limiting MCB at the meter, in fixed levels such as 1,300, 2,200 or 3,500 VA. To choose a PLN level, use the home connection & MCB calculator.
Which power factor should I enter?
Heaters, irons and incandescent lamps are close to 1. Motors, air-conditioner compressors and pumps are usually 0.8–0.9. When unsure, use 0.85 so the current is not underestimated.
Does this replace an electrician?
No. Breaker selection also depends on the cable, the type of load, the fault current and local rules. Use the result for planning, and have a licensed electrician check it before installation.
Related calculators
- PLN Home Connection & MCB (Indonesia)The single- or three-phase PLN connection needed for appliances running at once, with its MCB.Example: Recommended PLN connection4,400 VACalculate →
- Cable Voltage DropDC, single- and three-phase voltage drop and the smallest suitable cable.Example: Voltage drop10.08 VCalculate →
- Single & Three-Phase PowerkW, kVA, kVAR and current from voltage and power factor, plus correction capacitors.Example: Apparent power18.75 kVACalculate →