Cable Voltage Drop Calculator
DC, single- and three-phase voltage drop and the smallest suitable cable.
- Voltage at the load
- 209.92 V
- Power lost in the cable
- 161.3 W
- Smallest size for ≤ 3% drop
- 4 mm²
- Smallest size for ≤ 5% drop
- 2.5 mm²
Drop by cable size
| Size | Drop (V) | Drop (%) |
|---|---|---|
| 1.5 mm² | 16.8 | 7.64 |
| 2.5 mm² | 10.08 | 4.58 |
| 4 mm² | 6.3 | 2.86 |
| 6 mm² | 4.2 | 1.91 |
| 10 mm² | 2.52 | 1.15 |
| 16 mm² | 1.575 | 0.72 |
Formula and sources
DC and single phase: ΔV = 2 × L × I × ρ ÷ A Three phase: ΔV = √3 × L × I × ρ ÷ A ρ copper 0.0175 and aluminium 0.0282 Ω·mm²/m (about 20 °C); L = one-way length, A = cross-section Power lost = I² × resistance of all conductors
- PUIL 2011 (SNI 0225:2011) — Indonesian general electrical installation rules
When to use the Cable Voltage Drop
Long runs to a pump or shed
A 45 m run of 2.5 mm² cable carrying 16 A at 220 V loses about 10 volts, nearly 5%. The calculator shows the cable size that keeps the drop under 3%.
Low-voltage DC systems
At 12 V, a few volts of drop is already huge. LED lighting, DC pumps and small solar systems need bigger cables than people expect.
Three phase for machines
For balanced three-phase loads the multiplier is √3, not 2. Enter the current per phase and the line-to-line voltage.
Power lost as heat
Voltage drop means energy wasted in the cable. The calculator works out the watts lost, useful when judging the savings of a larger cable.
Frequently asked questions
How much voltage drop is acceptable?
As a general guide, the drop to the load should stay within about 3–5% of the nominal voltage. Sensitive equipment and motors need less.
Why is the length doubled?
In DC and single-phase circuits current flows out and back, so the total conductor length is twice the distance to the load.
Is cable reactance included?
No. For small and medium cables resistance dominates. For large AC cables above about 50 mm², reactance starts to matter and a detailed calculation is needed.
Does aluminium cable need to be larger?
Yes. Aluminium's resistance is about 1.6 times copper's, so for the same drop the cross-section must be about 1.6 times larger. Aluminium is lighter and cheaper and common in large distribution cables.
Related calculators
- Single & Three-Phase PowerkW, kVA, kVAR and current from voltage and power factor, plus correction capacitors.Example: Apparent power18.75 kVACalculate →
- Ohm's LawVoltage, current, resistance and power from any two known values.Example: Current0.054545 ACalculate →
- Generator SizeGenerator kVA from load, power factor, loading limit and motor starting.Example: Minimum generator size36.25 kVACalculate →