Cable Voltage Drop Calculator

DC, single- and three-phase voltage drop and the smallest suitable cable.

Calculated in your browserElectrical & Energy
Units
V
A
m
Voltage drop
10.08 V
Voltage drop (%)
4.58%
Voltage at the load
209.92 V
Power lost in the cable
161.3 W
Smallest size for ≤ 3% drop
4 mm²
Smallest size for ≤ 5% drop
2.5 mm²

Drop by cable size

SizeDrop (V)Drop (%)
1.5 mm²16.87.64
2.5 mm²10.084.58
4 mm²6.32.86
6 mm²4.21.91
10 mm²2.521.15
16 mm²1.5750.72

Formula and sources

DC and single phase: ΔV = 2 × L × I × ρ ÷ A Three phase: ΔV = √3 × L × I × ρ ÷ A ρ copper 0.0175 and aluminium 0.0282 Ω·mm²/m (about 20 °C); L = one-way length, A = cross-section Power lost = I² × resistance of all conductors

  • PUIL 2011 (SNI 0225:2011) — Indonesian general electrical installation rules

When to use the Cable Voltage Drop

  • Long runs to a pump or shed

    A 45 m run of 2.5 mm² cable carrying 16 A at 220 V loses about 10 volts, nearly 5%. The calculator shows the cable size that keeps the drop under 3%.

  • Low-voltage DC systems

    At 12 V, a few volts of drop is already huge. LED lighting, DC pumps and small solar systems need bigger cables than people expect.

  • Three phase for machines

    For balanced three-phase loads the multiplier is √3, not 2. Enter the current per phase and the line-to-line voltage.

  • Power lost as heat

    Voltage drop means energy wasted in the cable. The calculator works out the watts lost, useful when judging the savings of a larger cable.

Frequently asked questions

How much voltage drop is acceptable?

As a general guide, the drop to the load should stay within about 3–5% of the nominal voltage. Sensitive equipment and motors need less.

Why is the length doubled?

In DC and single-phase circuits current flows out and back, so the total conductor length is twice the distance to the load.

Is cable reactance included?

No. For small and medium cables resistance dominates. For large AC cables above about 50 mm², reactance starts to matter and a detailed calculation is needed.

Does aluminium cable need to be larger?

Yes. Aluminium's resistance is about 1.6 times copper's, so for the same drop the cross-section must be about 1.6 times larger. Aluminium is lighter and cheaper and common in large distribution cables.