Single & Three-Phase Power Calculator (kW, kVA, Amps)
kW, kVA, kVAR and current from voltage and power factor, plus correction capacitors.
- Real power
- 15 kW
- Reactive power
- 11.25 kVAR
- Capacitor for cos φ 0.95
- 6.3197 kVAR
Formula and sources
Single phase: S = V × I; three phase: S = √3 × V × I (line voltage) P = S × cos φ; Q = S × sin φ Correction capacitor: Qc = P × (tan φ₁ − tan φ₂)
- AC power theory — the P, Q, S power triangle
When to use the Single & Three-Phase Power
Three-phase motor current
A 15 kW motor at 380 V with cos φ 0.8 draws about 28.5 A per phase. The figure is used to choose cable, contactors and protection.
kW, kVA and kVAR
kW is the power that does work, kVA is what the network must carry, and kVAR is the reactive power for motors' magnetic fields. Generators and transformers are rated in kVA.
Correcting the power factor
A low power factor means more current for the same real power. The calculator works out the capacitor kVAR needed to raise cos φ to a target.
Reading equipment nameplates
Machine nameplates usually give power in kW, the voltage and cos φ. Enter all three to find the current the installation must supply.
Frequently asked questions
What power factor is typical?
Heaters and incandescent lamps are close to 1, motors are usually 0.75–0.9, and electronics with power-factor correction about 0.95 or more.
Why does PLN rate supplies in VA?
Network and protection must carry the total current, including reactive current, so connection capacity is stated as apparent power (VA), not watts.
Do capacitors cut household bills?
For homes usually not, because household meters record kWh. Industrial customers charged for excess kVARh benefit far more from power-factor correction.
How many amps does a 7.5 kW three-phase motor draw?
The nameplate power is shaft output, so divide by the efficiency first, say 0.9, giving about 8.33 kW input. At 380 V and a 0.85 power factor that is about 15 A per phase.
When does a low power factor cost money?
PLN's tariff rules charge certain classes, mainly business and industry, for excess kVARh when the monthly average power factor is below 0.85, meaning kVARh above 0.62 × kWh. Correction capacitors raise the power factor so the charge goes away.
Related calculators
- Generator SizeGenerator kVA from load, power factor, loading limit and motor starting.Example: Minimum generator size36.25 kVACalculate →
- Cable Voltage DropDC, single- and three-phase voltage drop and the smallest suitable cable.Example: Voltage drop10.08 VCalculate →
- Ohm's LawVoltage, current, resistance and power from any two known values.Example: Current0.054545 ACalculate →