Generator Size Calculator (kVA)

Generator kVA from load, power factor, loading limit and motor starting.

Calculated in your browserElectrical & Energy
W
%
Diesel generators run best at about 70–80% of capacity.
W
×
Direct-on-line 5–7×, star-delta about 2–3×, soft starter 2–3×, VFD about 1.5×.
L/kWh
Usually 0.25–0.35 litres per kWh; see the maker's data.
Minimum generator size
36.25 kVA
Nearest standard rating
40 kVA
Running load
22.5 kVA
Demand while the motor starts
36.25 kVA
Loading at the standard rating
56.3%
Estimated diesel per hour
4.5 litres

Generator sizes around the need

Size (kVA)Loading (%)Motor start
20112.5too small
2590too small
3075too small
4056.3enough
5045enough
6037.5enough
7530enough
8028.1enough

Formula and sources

Running kVA = load (W) ÷ power factor ÷ 1,000 Running need = running kVA ÷ loading limit Starting need = (other loads + largest motor × starting multiple) ÷ power factor ÷ 1,000 Minimum generator = max(running need, starting need)

  • ISO 8528-1 — reciprocating generating sets (prime and standby ratings)

When to use the Generator Size

  • Backup power for homes and shops

    Add up the appliances that must keep running in an outage and enter the power factor. The calculator leaves headroom so the generator is not worked too hard.

  • The surge when a motor starts

    Pumps, compressors and machines draw several times their current when starting. A generator big enough for the running load can still fail to start a large motor if the surge is ignored.

  • Picking a standard size

    Generators come in set kVA ratings. The table shows the loading of each size around your need and whether it can start the motor.

  • Estimating diesel cost

    With the fuel use per kWh from the maker's data, the calculator estimates litres of diesel per hour at that load to work out running costs.

Frequently asked questions

Why not load a generator to 100%?

Continuous loading near full capacity speeds wear and makes the voltage dip when the load jumps. A 70–80% limit leaves healthy headroom.

Which power factor should I use?

Generators are usually rated at a 0.8 power factor. Household loads with many electronics and lamps can be higher, motor loads about 0.8.

Are inverter generators different?

Small inverter generators give a cleaner voltage for sensitive electronics, but limited motor-starting power. Check the peak rating in the specs.

What generator size suits a 2,200 VA home?

To carry the full 2,200 VA at an 80% loading limit you need 2.2 ÷ 0.8 = 2.75 kVA, so a 3.5 kVA generator is enough. Add the starting surge of a water pump or air conditioner if there is one.

What is the difference between kW and kVA on a generator?

kVA is apparent power and kW is real power. At the 0.8 power factor generators are rated at, a 10 kVA generator gives 8 kW.