CCTV UPS & Battery Backup Calculator
Calculate CCTV camera, NVR, and PoE switch UPS apparent power (VA) and deep-cycle VRLA battery capacity (Ah) for power outage runtime.
Input Parameters
Calculation Results
- Number of IP Cameras
- 16 Cameras
- Power per CCTV Camera (IR Active)
- 7.5 Watts
- Total Camera Power Load
- 120 Watts
- Number of HDD Bays in NVR
- 2 HDDs
- NVR Unit + HDD Power Load
- 36 Watts
- Number of PoE Switch Units
- 1 Units
- PoE Switch Base Power Draw
- 12 Watts
- Total CCTV System Power Load
- 168 Watts
- Minimum Required UPS Rating (+Margin)
- 312 VA
- Recommended Commercial UPS Size
- 650 VA
- Target Outage Backup Duration
- 4 Hours
- DC Battery System Voltage
- 12 Volts
- Required VRLA Battery Capacity
- 83 Ah
- 12V Battery Units per String
- 1 Units
Use 24/7 CMR surveillance drives in NVRs and solid bare copper Cat6 for PoE runs exceeding 50 meters.
Ringkasan Backup UPS & Baterai Aki CCTV – InfraCalc.web.id Perangkat Aktif: 16 Kamera (@7.5W) + NVR (2 HDD) + 1 Unit Switch Total Beban : 168 Watt Kontinu 24/7 Target Backup : 4 Jam tetap merekam saat listrik PLN padam Rekomendasi UPS: Minimal 650 VA (Wajib Pure Sinewave + External Battery / DC Power Backup) Kapasitas Aki : 1× Aki VRLA Deep-Cycle 12V @ minimal 83 Ah (Sistem 12V DC)
Visual 2D 19" Server Rack & Patch Panel Builder
- 1U–4U (Bottom): Heavy UPS & VRLA Battery Banks mounted at the bottom to lower center of gravity.
- Middle: Compute servers, ZFS storage arrays, and NVRs placed in the center cold-aisle zone.
- Top: Top-of-Rack PoE switches, Cat6 patch panels, and brush organizers for overhead cable trays.
Generate Project BoQ / Cost Estimate (RAB)
| Kode | Material & Equipment | Qty (+15%) | Unit | Unit Price (IDR) | Line Total (IDR) |
|---|---|---|---|---|---|
| UPS-UNIT | Online Pure Sinewave Rackmount UPS (2200 VA) Pure Sinewave, PF 0.8–0.9, AVR | 1 | Unit | Rp 6.800.000 | |
| BATT-VRLA | 12V VRLA Deep-Cycle Battery Bank (~100 Ah Total) Maintenance-Free VRLA Battery | 2 | Unit | Rp 3.700.000 | |
| SRV-DISK | Enterprise NAS / Server Storage Drive & Railkit CMR 7200 RPM 24/7 Enterprise Grade | 4 | Unit | Rp 11.800.000 | |
| RACK-PDU | 19" Server Rack Cabinet + Metered PDU + C13/C14 Cords Includes grounding bar & roof fan unit | 2(Base: 1) | Paket | Rp 9.700.000 | |
| Equipment & Material Subtotal: | Rp 32.000.000 | ||||
| Estimated Installation & Commissioning (10%): | Rp 3.200.000 | ||||
| PPN (11%): | Rp 3.872.000 | ||||
| ESTIMATED GRAND TOTAL: | Rp 39.072.000 | ||||
Note: Unit prices above are initial reference estimates and can be edited inline.Referensi Teknis & BoQ — Built for Network & System Engineers
Technical Accuracy Note: Calculation results are engineering estimates based on standard RFC/IEEE/ITU-T models. Actual field performance may vary due to protocol overhead, hardware specifications, and environmental factors.
How to Use This Tool
- Input total active CCTV cameras and specify average camera night-time power draw in Watts.
- Specify the number of installed NVR hard drives, active PoE switches, and desired backup runtime in hours during power outages.
- Select the DC battery bus voltage (12V, 24V, or 48V) to review recommended UPS VA sizing and battery bank Ampere-hour (Ah) capacities.
Worked Example: Standard 16-Camera 1080p 4-Hour Backup (12V)
Worked example: A 16-camera setup (@7.5W) with an NVR (2 HDDs) and 1 PoE switch draws a total continuous load of 168 Watts. To sustain non-stop recording for 4 hours during a blackout mandates a UPS of at least 650 VA paired with a 1× 12V VRLA battery bank rated for at least 83 Ah (12V DC system).
- Active IP Camera Count
- 16 Cameras
- Night-Time Power per Camera
- 7.5 Watts
- NVR Hard Drive Count
- 2 HDDs
- PoE Switch Appliance Count
- 1 Units
- Target Backup Runtime
- 4 Hours
- DC Battery Bus Voltage
- 12V DC (1× 12V Battery - Compact Systems)
- Number of IP Cameras
- 16 Cameras
- Power per CCTV Camera (IR Active)
- 7.5 Watts
- Total Camera Power Load
- 120 Watts
- Number of HDD Bays in NVR
- 2 HDDs
- NVR Unit + HDD Power Load
- 36 Watts
- Number of PoE Switch Units
- 1 Units
- PoE Switch Base Power Draw
- 12 Watts
- Total CCTV System Power Load
- 168 Watts
- Minimum Required UPS Rating (+Margin)
- 312 VA
- Recommended Commercial UPS Size
- 650 VA
- Target Outage Backup Duration
- 4 Hours
- DC Battery System Voltage
- 12 Volts
- Required VRLA Battery Capacity
- 83 Ah
- 12V Battery Units per String
- 1 Units
- Material Requirement Summary (Copy-Ready)
- Ringkasan Backup UPS & Baterai Aki CCTV – InfraCalc.web.id Perangkat Aktif: 16 Kamera (@7.5W) + NVR (2 HDD) + 1 Unit Switch Total Beban : 168 Watt Kontinu 24/7 Target Backup : 4 Jam tetap merekam saat listrik PLN padam Rekomendasi UPS: Minimal 650 VA (Wajib Pure Sinewave + External Battery / DC Power Backup) Kapasitas Aki : 1× Aki VRLA Deep-Cycle 12V @ minimal 83 Ah (Sistem 12V DC)
Core Concept & Engineering Notes
How It Was Calculated (Formulas & Steps)
Mathematical Formulas
- Total System Load (W) = (Cameras × Power W) + (NVR Base 18W + HDDs × 9W) + (PoE Switches × 12W)
- Recommended UPS Apparent Power (VA) = ceil((Total Watts × 1.3 Safety Margin) ÷ 0.7 Power Factor)
- Battery Bank Capacity (Ah) = ceil((Total Watts × Backup Hours) ÷ (DC Bus Volts × 0.85 Inverter × 0.80 DoD))
- 12V Battery Series Units = round(DC Bus Volts ÷ 12)
Step-by-Step Calculation
- 1. Active CCTV System Load: Cameras (16 × 7.5W = 120W) + NVR (Base 18W + 2 HDDs × 9W = 36W) + PoE Switches (1 × 12W = 12W) = 168 Watts continuous
- 2. Minimum UPS Capacity: (168 W × 1.3 safety margin) / 0.7 power factor = 312 VA -> Selected standard rating: 650 VA
- 3. Battery Energy Requirement: (168 W × 4 hours) = 672 Watt-hours
- 4. VRLA Battery Bank Sizing: (672 Wh) / (12V DC bus × 0.85 inverter efficiency × 0.80 Depth of Discharge DoD) = 83 Ah
- 5. Battery Bank Configuration: 1× 12V series batteries yielding 12V DC bus at 83 Ah
Frequently Asked Questions (FAQ)
Why are standard desktop office UPS units unsuitable for CCTV installations?
Standard consumer UPS units are designed exclusively for 5–10 minutes of runtime to allow graceful operating system shutdown. Furthermore, budget units output simulated modified sinewaves, which generate harmonic distortion, electrical hum, and premature failure across sensitive PoE switch power supplies.
What is the difference between 12V, 24V, and 48V battery bus systems on a UPS?
Higher DC bus voltages (e.g. 48V DC constructed by four 12V batteries in series) divide current proportionally for an identical power load. This substantially reduces resistive I²R heat generation in battery cables and boosts inverter efficiency across large CCTV deployments.
Why is battery Depth of Discharge (DoD) capped at a maximum of 80%?
Discharging lead-acid (VRLA/AGM) batteries down to 100% capacity triggers irreversible lead sulfation across internal plates, degrading operational lifespan from hundreds of cycles down to a few dozen. Limiting discharge to 80% DoD preserves battery health over 3 to 5 years.
Related Calculators
View All CCTV, PoE & Fiber Tools →Calculate server UPS capacity (kVA/VA), VRLA battery runtime (Ah), and 24/7 monthly electricity cost with 25% safety margin and power factor.
Calculate PoE Cat6, Cat5e, and CCA cable voltage drop, delivered terminal voltage, safe run distances, and night-time infrared reboot risks.
Calculate CCTV NVR storage capacity (TB), network ingress bandwidth Mbps, recording retention days, PoE budgets, and surveillance HDD recommendations.
Calculate CCTV lens focal length recommendations (2.8mm, 4mm, 6mm, 12mm), field of view coverage width, and DORI pixel density per target distance.
Calculate EN 62676-4 CCTV DORI detection, observation, recognition, and facial identification reach distances based on sensor resolution and lens optics.
Estimate CCTV installation material Bill of Materials (BOM): Cat6 UTP cable boxes, RJ45 modular plugs, junction boxes, conduit pipes, and cable ties.
References & Notes
- IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications (IEEE 485)
- APC by Schneider Electric CCTV and Security Power Protection White Paper
- NFPA 731: Standard for the Installation of Electronic Premises Security Systems
Note: Results above are mathematical estimates based on standard formulas. Always verify against official vendor documentation and site conditions before production deployment.
🔗Related Scenarios & Companion Calculators
Browse All 30+ Scenarios →⚡ Ready-to-Use Scenario Presets:
How much HDD storage do 16 1080p CCTV cameras need for 30 days 24/7? Compare H.265 (~4.2 TB) vs H.264 (~8.4 TB) NVR requirements.
Calculate exact HDD size for 8 CCTV cameras recording 30 days 24/7. Requires ~2.1 TB with H.265 (use a 4 TB HDD).
🛠️ Sibling Calculators in this Category:
Calculate CCTV lens focal length recommendations (2.8mm, 4mm, 6mm, 12mm), field of view coverage width, and DORI pixel density per target distance.
Calculate EN 62676-4 CCTV DORI detection, observation, recognition, and facial identification reach distances based on sensor resolution and lens optics.
Calculate PoE Cat6, Cat5e, and CCA cable voltage drop, delivered terminal voltage, safe run distances, and night-time infrared reboot risks.
Calculate CCTV NVR storage capacity (TB), network ingress bandwidth Mbps, recording retention days, PoE budgets, and surveillance HDD recommendations.
Engineering Sensitivity Analysis, Response Curve & Technical Citation
1. 1. 3-Point Engineering Sensitivity & Tolerance Envelope
Comparative evaluation across theoretical laboratory bounds (0% loss), current nominal operating point, and conservative field safety bounds (±15% thermal/aging derating).
| Evaluated Parameter | Ideal Theoretical Bound | Nominal Operating Point | Conservative Safety Bound (±15%) | Engineering Derating Rule |
|---|---|---|---|---|
| Number of IP Cameras | 14.4 | 16 | 18.4 | Engineering Safety Margin (+15% Overhead) |
| Power per CCTV Camera (IR Active) | 6.75 | 7.5 | 8.63 | Engineering Safety Margin (+15% Overhead) |
| Total Camera Power Load | 108 | 120 | 138 | Engineering Safety Margin (+15% Overhead) |
| Number of HDD Bays in NVR | 1.8 | 2 | 2.3 | Engineering Safety Margin (+15% Overhead) |
| NVR Unit + HDD Power Load | 32.4 | 36 | 41.4 | Engineering Safety Margin (+15% Overhead) |
2. 2. Mathematical Function Curve & Operating Coordinate (x₀, y₀)
3. 3. Physical Constants & Normative Standard Clauses
Minimum Horizontal Pixel Density for Identification (DORI)
Clause 6.5 & Table A.1 (25 / 62 / 125 / 250 px/m) — Video surveillance standard specifies Detection=25 px/m, Observation=62 px/m, Recognition=125 px/m, Identification=250 px/m.
DC Loop Resistance for 23 AWG Solid Copper Cat6
Clause 6.4.1 / Table 145-1 — Nominal 23 AWG solid copper loop resistance at 20°C is 14.0 Ω/100m (TIA maximum ceiling is 18.8 Ω/100m).
Temperature Coefficient of Resistance for Copper
International Annealed Copper Standard — Used in thermal derating equation: R(T) = R_20 × [1 + 0.00393 × (T - 20)].
4. 4. Independent Technical & Academic Citation (IEEE / APA 7th / BibTeX / LaTeX)
Use the standard citation formats below to reference this computational methodology in engineering specifications, audit reports, or academic papers.
[IEEE] KalkuNet Engineering Team, "CCTV UPS & Battery Backup Calculator — Standard Engineering Computational Instrument," KalkuNet Technical Suite, 2026. [Online]. Available: https://kalkunet.com/en/tools/cctv-ups-calculator. [Accessed: 2026-11-08].
[APA 7th] KalkuNet Engineering Team. (2026). CCTV UPS & Battery Backup Calculator (Production release 2026-11-08) [Engineering computational software]. KalkuNet. https://kalkunet.com/en/tools/cctv-ups-calculator
@software{kalkunet_cctv_ups_calculator_2026,
author = {{KalkuNet Engineering Team}},
title = {{CCTV UPS & Battery Backup Calculator --- KalkuNet Engineering Suite}},
year = {2026},
publisher = {KalkuNet.com},
url = {https://kalkunet.com/en/tools/cctv-ups-calculator},
urldate = {2026-11-08}
}
% LaTeX Engineering Derivation — Generated via https://kalkunet.com/en/tools/cctv-ups-calculator
\begin{equation}
\text{Model: } Total System Load (W) = (Cameras × Power W) + (NVR Base 18W + HDDs × 9W) + (PoE Switches × 12W)
\end{equation}
% Parameter Input Terukur: camCount = 16, \; camWatt = 7.5, \; nvrHddCount = 2, \; poeSwitches = 1
% Hasil Evaluasi Numerik : camCount = \mathbf{16}, \; camWatt = \mathbf{7.5}, \; totalCamsWatt = \mathbf{120}